Danfoss VLT® Micro Drive FC051 Variable Frequency Drives are no longer manufactured or supplied as part of the current product portfolio. The FC51 series has entered the Limited phase of its product lifecycle, and the Danfoss iC2-Micro is now its official successor.
For industrial facilities with FC-051 drives already installed, this means that replacing a failed unit with an identical new model may no longer be possible. Instead, an appropriate iC2-Micro drive must be selected and checked for compatibility with the motor, control circuit, and existing automation system.
This article explains:
- what to use as a replacement for the Danfoss FC 51;
- how to select the correct iC2-Micro model;
- which parameters must be checked before replacement;
- whether the existing PLC program can be retained;
- whether a fully operational FC 51 should be replaced;
- how to use the FC51 to iC2-Micro cross-reference table.
Which variable frequency drive replaces the Danfoss FC-051?
The official successor to the Danfoss VLT® Micro Drive FC 51 is the Danfoss iC2-Micro. Danfoss positions the iC2-Micro as a compact general-purpose Variable Frequency Drive for pumps, fans, conveyors, compressors, mixers, and other low- and medium-power machinery. The iC2-Micro was developed with retrofit applications in mind, including machines and systems that currently use FC 51 drives. The new series retains the core functions required for typical industrial applications while introducing a more modern hardware platform, a new ordering-code structure, and a different parameter architecture.
The main available iC2-Micro ranges include:
- single-phase 200–240 V supply: 0.37 to 2.2 kW;
- three-phase 380–480 V supply: 0.37 to 22 kW.
The iC2-Micro therefore covers the main power range previously served by the FC51.
Is the iC2-Micro a Direct Replacement for the FC051?
The iC2-Micro is the official successor to the FC 51. However, the term direct replacement does not mean that a new drive can always be selected solely by matching the power rating in kilowatts. For example, if a machine is fitted with a 4 kW FC 51, simply ordering a 4 kW iC2-Micro may not be sufficient.
The following parameters must also be checked:
- supply voltage;
- rated output current;
- motor rated current;
- overload capability;
- availability of a brake chopper;
- EMC category;
- number and type of inputs and outputs;
- control method;
- use of Modbus RTU communication;
- physical dimensions of the new drive;
- installation and cooling conditions.
- The cross-reference table should therefore be treated as a starting point. Final selection must be based on the requirements of the specific application.
Danfoss FC 51 to iC2-Micro Cross-Reference Table
| FC 51 Ordering Code | FC 51 Type Code | iC2-Micro Ordering Code | iC2-Micro Type Code |
|---|---|---|---|
| 132F0001 | FC-051PK18S2E20H3XXCXXXSXXX | 132L6110 | IC2-30FA1N02-02A2E20F0+ACXX |
| 132F0002 | FC-051PK37S2E20H3XXCXXXSXXX | 132L6110 | IC2-30FA1N02-02A2E20F0+ACXX |
| 132F0003 | FC-051PK75S2E20H3XXCXXXSXXX | 132L6111 | IC2-30FA1N02-04A2E20F0+ACXX |
| 132F0005 | FC-051P1K5S2E20H3BXCXXXSXXX | 132L6112 | IC2-30FA1N02-06A8E20F0+ACXX |
| 132F0007 | FC-051P2K2S2E20H3BXCXXXSXXX | 132L6115 | IC2-30FA1N02-09A6E20F0+ACXX |
| 132F0017 | FC-051PK37T4E20H3XXCXXXSXXX | 132L6128 | IC2-30FA3N04-01A2E20F2+ACXX |
| 132F0018 | FC-051PK75T4E20H3XXCXXXSXXX | 132L6129 | IC2-30FA3N04-02A2E20F2+ACXX |
| 132F0020 | FC-051P1K5T4E20H3BXCXXXSXXX | 132L6130 | IC2-30FA3N04-03A7E20F2+ACXX |
| 132F0022 | FC-051P2K2T4E20H3BXCXXXSXXX | 132L6131 | IC2-30FA3N04-05A3E20F2+ACBC |
| 132F0024 | FC-051P3K0T4E20H3BXCXXXSXXX | 132L6132 | IC2-30FA3N04-07A2E20F2+ACBC |
| 132F0026 | FC-051P4K0T4E20H3BXCXXXSXXX | 132L6133 | IC2-30FA3N04-09A0E20F2+ACBC |
| 132F0028 | FC-051P5K5T4E20H3BXCXXXSXXX | 132L6134 | IC2-30FA3N04-12A0E20F2+ACBC |
| 132F0030 | FC-051P7K5T4E20H3BXCXXXSXXX | 132L6135 | IC2-30FA3N04-15A5E20F2+ACBC |
| 132F0058 | FC-051P11KT4E20H3BXCXXXSXXX | 132L6136 | IC2-30FA3N04-23A0E20F2+ACBC |
| 132F0059 | FC-051P15KT4E20H3BXCXXXSXXX | 132L6137 | IC2-30FA3N04-31A0E20F2+ACBC |
| 132F0060 | FC-051P18KT4E20H3BXCXXXSXXX | 132L6138 | IC2-30FA3N04-37A0E20F2+ACBC |
| 132F0061 | FC-051P22KT4E20H3BXCXXXSXXX | 132L6139 | IC2-30FA3N04-43A0E20F2+ACBC |
When using the table, first identify the ordering code of the installed FC 51. This information is shown on the drive nameplate and normally includes:
- a Danfoss product code beginning with 132F…;
- the complete FC 51 type designation beginning with FC-051….
Once the installed drive has been identified, verify:
- supply voltage;
- power rating;
- rated output current;
- drive configuration;
- additional functions used in the control system.
Particular care is required when the motor operates under heavy load, frequent acceleration and deceleration, braking cycles, or high starting-torque conditions. In these applications, selecting the replacement drive solely by matching the kilowatt rating may result in the new drive being undersized or repeatedly overloaded.
What has changed in the iC2-Micro compared with the FC51?
The iC2-Micro is not simply an FC51 installed in a new enclosure. It is a different drive platform with updated electronics, a new user interface, and enhanced control capabilities.
Frequently asked questions
What should I use to replace a Danfoss FC-051?
The official successor to the Danfoss VLT® Micro Drive FC 51 is the Danfoss iC2-Micro. The specific replacement model should be selected based on:
- supply voltage;
- rated output current;
- motor power;
- overload capability;
- configuration of the existing drive.
Is the Danfoss FC 51 still available?
The FC51 is no longer part of Danfoss’s current active product portfolio and is no longer in active production. The series has entered the Limited phase of its product lifecycle. For new projects and replacement applications, Danfoss recommends the iC2-Micro.
Can I install an iC2-Micro with the same power rating?
Not always. In addition to power rating, the following parameters must be compared:
- rated output current;
- supply voltage;
- overload capability;
- braking functions;
- EMC configuration;
- ambient and installation conditions.
For heavily loaded applications, rated current and overload performance may be more important than the nominal kilowatt rating.
Are the FC 51 and iC2-Micro Terminals the Same?
No. The functional assignment of the terminals must be compared using the relevant technical documentation. Wires must not be transferred solely on the basis of matching terminal numbers, as the same terminal number may serve a different function on the new drive.
Does the electrical diagram need to be modified?
The power circuit may remain similar, but the control circuit must be checked.
The following may differ:
- terminal numbers;
- digital input and output assignments;
- analogue input and output functions;
- sensor supply connections;
- relay assignments;
- RS-485 wiring.
The final scope of changes depends on how the FC 51 is integrated into the existing machine or control cabinet.
Can FC 51 Parameters Be Copied Directly to the iC2-Micro?
Not automatically.
The FC 51 settings should first be recorded or backed up. The required values must then be transferred to the corresponding iC2-Micro parameters, taking into account the different menu and parameter structure.
The following settings should be checked carefully:
- motor nameplate data;
- minimum and maximum frequency;
- acceleration and deceleration times;
- current and torque limits;
- start and stop logic;
- PID settings;
- input and output assignments;
- communication parameters;
- protection and alarm settings.
Does the PLC Program Need to Be Changed?
Not always. For systems using discrete and analogue control signals, it may be sufficient to configure the iC2-Micro inputs and outputs correctly.
For installations using Modbus RTU, the following must be checked:
- register addresses;
- communication format;
- control and status words;
- data scaling;
- baud rate;
- parity;
- device address;
- timeout behaviour.
Depending on the existing configuration, the PLC program may remain unchanged or require minor modifications.
Conclusion
The Danfoss VLT® Micro Drive FC51 is no longer manufactured as part of the current Variable Frequency Drive portfolio. Its official successor is the Danfoss iC2-Micro, which is designed for typical pump, fan, conveyor, compressor, mixer, and other general industrial applications. The cross-reference table above can be used to identify a basic iC2-Micro replacement based on the FC 51 ordering code. For non-standard, heavily loaded, or production-critical machinery, compatibility should always be verified individually.
Technosens engineers can help select the correct Danfoss iC2-Micro replacement for an FC 51, verify technical compatibility, identify the required control-circuit modifications, and prepare the new drive parameters for commissioning.