Project

Manufacturing a control cabinet for two 200 kW pump sets for Sumy city water utility

Technosens LLC designed and manufactured a control cabinet for two 200 kW pumping units for Sumy City Water Utility, operated by the Sumy City Council. The system is built around a single Danfoss VLT® AQUA Drive FC 202 Variable Frequency Drive and provides alternating operation of two pumps. Each pump can operate either through the Variable Frequency Drive or directly from the mains in bypass mode. Electrical and mechanical interlocks prevent simultaneous operation of both pump sets.

Project information:
Design and manufacture of a control cabinet for alternating control of two 200 kW pumping units with variable speed control, automatic pressure regulation, and a backup operating mode that allows the pumps to run without the Variable Frequency Drive.

Industry:

Water Supply • Critical Infrastructure

Customer:

Municipal Enterprise of the Sumy City Council

Date:

09/07/2026

The main goals of the project are:

  • automate the operation of borehole pumping units;
  • maintain constant pressure within the water supply network;
  • provide automatic alternation between duty and standby pumps;
  • ensure soft motor starting and variable speed control according to actual water demand;
  • enable pump operation in bypass mode during maintenance or failure of the Variable Frequency Drive;
  • provide reliable operation from both the utility grid and a standby generator;
  • protect pumps and motors against abnormal operating conditions;
  • prepare the system for future integration into a SCADA and remote monitoring system.

Composition of the system's hardware:

  • Danfoss VLT® AQUA Drive FC 202 Variable Frequency Drive, 200 kW, 3 × 380–480 V;
  • Eaton easy programmable control relay with digital I/O expansion module;
  • Novatek universal motor protection relay;
  • ETI power contactors with mechanical interlocking;
  • Phoenix Contact relay modules, terminal blocks, and power distribution blocks; current transformers;
  • forced ventilation and cabinet heating system with automatic temperature control;
  • manual control devices, status indication lamps, and an emergency stop pushbutton.

Results:

  • automatic maintenance of the required pressure within the water supply network;
  • smooth pump starting without high inrush currents or hydraulic shock;
  • automatic adjustment of pump capacity according to actual water consumption;
  • reduced energy consumption during partial-load operation through variable speed control;
  • more uniform operating hours of the pumping units through automatic alternation;
  • uninterrupted water supply during maintenance of the Variable Frequency Drive by operating the pumps in bypass mode;
  • comprehensive protection of motors against overload, phase loss, phase imbalance, short circuit, overheating, under-voltage, and over-voltage conditions;
  • reliable pump station operation from a standby generator;
  • improved operational reliability, serviceability, and long-term maintainability of the pumping station.