EEnovance 50 kW Energy Storage Systems: 61 kWh or 128 kWh
EEnovance 50 kW Energy Storage Systems: 61 kWh or 128 kWh

EEnovance 50 kW Energy Storage Systems: 61 kWh or 128 kWh

When a company starts selecting a Battery Energy Storage System (BESS), the first question is usually about power. Suppose the calculations show that 50 kW is sufficient to support the facility’s critical loads. That does not complete the selection process. The next question is how much energy storage capacity the facility actually needs: 61 kWh, 128 kWh, or more. The current range of EEnovance energy storage systems supplied by Technosens includes two solutions in this power class:
  • E-MATE 50-61-A — 50 kW / 61.4 kWh

  • E-MATE 50-128-A — 50 kW / 128 kWh

Both systems have the same power rating, but they may be suitable for very different applications.

50 kW and 50 kWh Are Not the Same Thing

This is where confusion often begins. 50 kW is the system’s power rating. It indicates how much load the BESS can supply at a given moment. 61 or 128 kWh is the battery’s energy storage capacity. It indicates how much energy the battery can store.

Put simply, power answers the question, “What equipment can we supply?” while energy capacity answers, “How long can we supply it?” That is why two 50 kW energy storage systems may be appropriate for completely different facilities.

E-MATE 50-61-A: 50 kW Power and 61.44 kWh Energy Capacity

The E-MATE 50-61-A is a compact commercial and industrial (C&I) energy storage system from EEnovance, rated at 50 kW with a battery capacity of 61.44 kWh. The battery uses lithium iron phosphate (LFP) cells and consists of 12 modules rated at 5.12 kWh each. The specified charge and discharge rate is 0.8P. However, battery capacity is only part of what makes this model interesting. The E-MATE 50-61-A features a hybrid architecture designed to integrate the utility grid, battery storage, solar PV panels, a diesel generator, and both critical and non-critical loads. On the PV side, the system provides four MPPT inputs, an operating voltage range of 150–850 V, and support for up to 75 kW of solar PV capacity. It supports both grid-connected and off-grid operation. This configuration is suitable for facilities where battery storage needs to work alongside other power sources rather than operate as a standalone system. For example, a facility may already have solar PV, a grid connection, and a diesel generator. During the day, solar generation supplies part of the load, while surplus energy can be stored in the battery for later use or kept in reserve. If the grid becomes unavailable, the battery provides an additional source of backup power.

Where Does the E-MATE 50-61-A Make Sense?

This model may be suitable for small manufacturing facilities, farms, warehouses, retail premises, offices, pumping stations, cold storage facilities, or businesses that already have solar PV or a diesel generator.  The key consideration is not the facility’s total electricity consumption, but the power demand of its critical loads. A facility with a total load of 150 kW does not necessarily need a 150 kW BESS. During a power outage, it may not be necessary to keep the entire production process running. For example, the priority may be to maintain power to automation equipment, servers, lighting, refrigeration systems, pumps, and several essential machines with a combined load of no more than 50 kW. In this situation, a 50 kW energy storage system may be a technically reasonable solution.

When 61 kWh Is Not Enough

A different situation arises when 50 kW of power is sufficient, but 61 kWh of stored energy is not. This is where the E-MATE 50-128-A becomes worth considering. The configuration currently offered by Technosens includes:

  • A 50 kW Power Conversion System (PCS)
  • Approximately 128 kWh of battery storage
  • 314 Ah LFP battery cells
  • Eight battery modules of approximately 16 kWh each
  • Air cooling

In this case, it is not the maximum output power that increases, but the amount of energy available. For the facility, this means potentially longer backup operation or more energy available for shifting consumption between charging and discharging periods.

Example: A 40 kW Critical Load

Suppose a facility identifies a group of critical loads with a combined power demand of approximately 40 kW.  If that load operates for one hour, it theoretically requires around 40 kWh of energy. For two hours, the requirement increases to approximately 80 kWh. With the same PCS power rating, a system equipped with a 128 kWh battery can therefore potentially provide significantly longer backup operation than one with a 61 kWh battery. However, actual backup runtime cannot be calculated simply by dividing nominal battery capacity by load power. A proper calculation must account for allowable depth of discharge, PCS efficiency, the system’s own energy consumption, actual load profile, reserved State of Charge (SOC), temperature, battery operating conditions, and motor starting or other short-duration peak loads. Backup runtime must always be calculated for the specific facility and its operating conditions.

When Is 61 kWh the Better Choice?

The E-MATE 50-61-A is worth considering when the main objective is not extended backup runtime, but flexible operation with multiple power sources. For example, a facility may already have solar PV, a grid connection, and a diesel generator. The BESS is needed to support critical loads during short power interruptions, store some of the solar energy generated during the day, and help coordinate the operation of different power sources. This is where the hybrid architecture of the E-MATE 50-61-A becomes particularly useful. The manufacturer also provides an intelligent Energy Management System (EMS), remote monitoring, and diagnostics. Safety is addressed through a multi-layer protection system incorporating gas detection, ventilation, and fire suppression.

When Should You Consider 128 kWh?

The E-MATE 50-128-A makes sense when the limiting factor is no longer output power, but operating time or the required energy reserve.

Typical scenarios include facilities that need to:

  • Keep critical loads running for longer periods.
  • Store more energy from an existing solar PV installation.
  • Shift a greater amount of electricity consumption between different times of day.
  • Support loads of 30–50 kW for several hours.
  • Build up a larger energy reserve ahead of scheduled power outages.

In such cases, automatically moving to a 100 or 125 kW PCS may not be justified if the facility does not actually need that much output power. A more appropriate solution may be to retain a 50 kW PCS and increase the battery capacity instead.

Where to Start When Selecting a BESS for Backup Power

If backup power is the primary objective, the selection process should begin with the critical loads, not with a particular equipment model.

Consider the following example:

Critical Equipment Power Demand
Automation systems and servers 5 kW
Lighting 3 kW
Pumps 12 kW
Refrigeration equipment 15 kW
Other critical loads 5 kW
Total 40 kW

The next step is to determine how long these 40 kW of critical loads must operate without grid power.  Thirty minutes? One hour? Two hours? Four hours? Only then can the required battery capacity be selected on a sound technical basis. This is why two facilities with identical 40 kW critical loads may need very different energy storage systems.

A BESS and Diesel Generator Can Work Together

In a conventional backup power arrangement, the diesel generator starts when grid power is lost. It needs time to start, reach its operating voltage and frequency, and accept the load. In addition, operating a diesel generator at low load is not always efficient or desirable. A hybrid power system allows these functions to be shared. The BESS can provide immediate support to critical loads, while the generator starts later and operates under more favorable loading conditions. The E-MATE 50-61-A is specifically designed to support integration with a diesel generator as part of its hybrid system architecture. For Ukrainian industrial facilities, this is a particularly practical application. Many businesses already have a generator installed. The objective is not necessarily to replace it, but to integrate it into a more flexible and reliable backup power system.

What If the Facility Already Has Solar PV?

Battery storage creates another opportunity. A solar PV system generates electricity according to solar irradiance, while industrial electricity consumption follows the facility’s production schedule. These two profiles often do not match. A battery makes it possible to partially separate generation from consumption in time: store surplus solar energy when it is available and use it later. This is a natural application for the E-MATE 50-61-A because PV integration is built directly into its hybrid architecture. The system supports up to 75 kW of solar PV capacity and provides four independent MPPT inputs.

61 kWh or 128 kWh: Which Should You Choose?

The distinction can be summarized quite simply. The E-MATE 50-61-A is suitable when the facility needs 50 kW of output power, a relatively compact energy reserve, and integrated operation with solar PV, the utility grid, battery storage, and a diesel generator. The E-MATE 50-128-A is worth considering when 50 kW of output power is sufficient, but the facility needs more stored energy. However, a model name and its rated specifications are not enough to make the final decision. The selection must take into account the actual load, required backup runtime, existing solar PV and generator installations, daily electricity consumption profile, and the specific operational problem the BESS is intended to solve. Only then can we determine whether 61 kWh is sufficient, whether 128 kWh is required, or whether the facility would benefit from an energy storage system in an entirely different power and capacity class.

Technosens supplies industrial EEnovance Battery Energy Storage Systems and selects the appropriate configuration based on each facility’s actual load profile, existing solar PV installation, generator, and required backup runtime.