An Energy Storage System for an industrial facility is more than just a battery rated in kWh
uze-eenovance-dlya-pidpryyemstv

An Energy Storage System for an industrial facility is more than just a battery rated in kWh

An energy storage system (ESS) for an industrial facility is not simply a battery whose capacity needs to be calculated in kWh. At one site, the ESS may be required to keep critical equipment operating during a power outage. At another, its primary purpose may be to store surplus energy generated by a solar PV system. Elsewhere, the main objective may be to reduce peak demand or enable production equipment to operate together with a diesel generator. That is why at Technosens, we do not begin ESS selection with the question: “How many kWh do you need?” The first step is to determine what exactly the energy storage system needs to do at the facility. For such projects, Technosens supplies industrial EEnovance energy storage systems. The manufacturer’s portfolio includes ready-to-deploy C&I solutions integrating LFP batteries, PCS, BMS, EMS, cooling, protection, and monitoring systems. In this article, we review several E-MATE configurations that we consider particularly practical for Ukrainian industrial and commercial facilities.

First, determine what actually needs backup power

A facility consumes 500 kW. Does that mean it needs a 500 kW ESS? Not necessarily. During a grid outage, there is often no need to keep the entire facility running. The critical loads may include a single production line, refrigeration equipment, automation systems, servers, pumps, ventilation systems, or another selected group of consumers. For example, the facility’s total load may be 500 kW, while only 120 kW is required to maintain the critical production process. That results in a completely different ESS configuration—and a completely different project budget. However, simply adding up the power ratings of all critical loads is not enough either. If compressors, pumps, refrigeration systems, or large electric motors are included, their starting method, starting current, and load characteristics must also be considered.

This is why selecting the right ESS for an industrial facility based solely on its monthly electricity bill is not possible.

ESS Power and Energy Capacity Are Not the Same

This is a fundamental distinction, but it is also where many mistakes begin during preliminary system selection. kW indicates how much power the system can deliver to the load. kWh indicates how much energy is stored in the battery. Two systems can therefore have the same power rating but provide completely different backup durations. For example, if the critical load is 40 kW, a 50 kW system may be sufficient. However, the required battery capacity will depend on whether that load needs to operate for tens of minutes or several hours. And this still does not account for allowable depth of discharge, system efficiency, reserve capacity, and the actual load profile.

Which EEnovance Energy Storage Systems does Technosens supply?

Our current offering focuses on several E-MATE systems.

Model Power Battery Capacity Cooling
E-MATE 50-61-A 50 kW 61.44 kWh Air-cooled
E-MATE 128-A up to 50 kW* up to 128.6 kWh
E-MATE 105-221-A 105 kW 221.056 kWh Air-cooled
E-MATE 125-261-L 125 kW 261.25 kWh Liquid-cooled
E-MATE 200-418-L 200 kW 418 kWh Liquid-cooled

* The E-MATE 128-A is available with hybrid inverter configurations in the 30–50 kW range. The specific configuration is selected according to project requirements.

E-MATE 50-61-A: Integrating PV, Battery Storage, Grid and Generator

The E-MATE 50-61-A is a compact 50 kW hybrid energy storage system with 61.44 kWh of battery capacity. What makes this model particularly interesting is its architecture. The system can integrate the utility grid, battery storage, solar PV generation, and a diesel generator. Four MPPTs are provided for PV integration, with a maximum solar generation capacity of 75 kW. The system supports both on-grid and off-grid operation, with the manufacturer specifying a transition time of less than 20 ms between operating modes. This makes the E-MATE 50-61-A worth considering for small manufacturing facilities, warehouses, agricultural businesses, retail facilities, pumping stations, and other sites where solar PV and backup generation are already installed or planned.

E-MATE 128-A: when energy capacity matters more

Consider a different scenario: the facility’s critical load does not exceed 30–50 kW, but it needs to remain operational for a longer period. In this case, there is no reason to automatically move to a 100 or 200 kW system. A larger battery may be the more appropriate solution. For this type of application, EEnovance offers the E-MATE 128-A, with battery capacity of up to 128.6 kWh and a 30–50 kW hybrid inverter. This is a good example of why an ESS must always be selected based on two parameters simultaneously: required power and required energy capacity.

E-MATE 105-221-A: more than just backup power

The E-MATE 105-221-A provides 105 kW of power and 221.056 kWh of battery capacity. The system uses LFP batteries, air cooling, an IP55 enclosure, and integrated control and protection systems. The manufacturer specifies a service life of up to 8,000 cycles under defined operating conditions. For a medium-sized industrial facility, a system of this class can be considered for more than emergency backup. Depending on the electrical architecture of the site, it can be used for:

  • storing locally generated solar energy;
  • time shifting;
  • peak shaving;
  • supporting critical production loads.

At this level, analysing the facility’s daily load profile becomes particularly important. Without it, accurately assessing the economic benefits of an ESS is virtually impossible.

E-MATE 125-261-L: Designed for Regular Cycling

The E-MATE 125-261-L combines 125 kW of power with 261.25 kWh of energy storage. A key difference compared with the previous systems is liquid cooling. When a battery is charged and discharged regularly, cell temperature directly affects its operating performance. For larger systems, it is therefore important not only to remove heat but also to maintain a uniform temperature across the battery modules. We consider this configuration suitable for manufacturing facilities, logistics and cold-storage complexes, facilities with their own solar PV generation, and other applications where the ESS is expected to operate regularly rather than simply remain on standby for the next grid outage.

E-MATE 200-418-L: For Higher Industrial Loads

The E-MATE 200-418-L provides 200 kW of power and 418 kWh of battery capacity. The system uses LFP batteries and liquid cooling and features an IP55 enclosure. CAN, RS485, and TCP interfaces are available for system integration and monitoring. One particularly interesting technical parameter is the manufacturer’s specified temperature difference between battery cells of ≤3°C, illustrating the practical value of liquid thermal management in energy storage systems of this size. The E-MATE 200-418-L can be considered for industrial sites, large cold-storage facilities, agricultural businesses, sites with high-capacity PV systems, and other facilities where a substantial group of loads must be supported.

What if the facility requires more than 200 kW?

EEnovance’s capabilities do not end with the E-MATE 200-418-L. The manufacturer also offers larger C&I energy storage solutions. The FlexCore platform, for example, includes systems with power ratings of up to 500 kW and energy capacities exceeding 1 MWh. Therefore, the 50–200 kW range covered in this article does not represent the upper limit of EEnovance technology. These are simply the configurations we have chosen to focus on in this overview. For larger industrial facilities, the ESS is engineered individually according to the site’s load profile and existing electrical infrastructure.

ESS, Solar PV and Generator Should Operate as One Integrated System

In practice, many Ukrainian industrial facilities already have a diesel generator. Increasingly, they also have their own solar PV system. The challenge is therefore not simply to install another energy source. The operating logic of the entire power system must be defined:

  • When should the battery be charged?
  • Which loads remain powered when the grid fails?
  • When should the generator start?
  • Can the generator supply the load and charge the ESS simultaneously?
  • How should available PV generation be utilized?
  • What happens when the utility grid is restored?

This is why an industrial energy storage system should not be viewed as a standalone battery cabinet. It is an integral part of the facility’s power supply infrastructure.

What information is required to select an ESS?

Even for a preliminary calculation, we need more than the desired kW and kWh ratings. Useful input data include:

  • daily or hourly load profile;
  • facility peak demand and incoming supply capacity;
  • list of critical loads;
  • power ratings and starting methods of the largest electric motors;
  • required backup duration;
  • parameters of the existing or planned solar PV system;
  • generator rating and technical characteristics;
  • required ESS functions: backup power, PV integration, peak shaving, time shifting, or several operating modes combined.

Once this information is available, the required PCS power, battery capacity, and specific EEnovance configuration can be determined more accurately. Sometimes the calculated system turns out to be smaller than the customer initially expected. Instead of backing up the entire facility, it may be more practical to identify a critical load group and design the ESS specifically around those consumers. In other cases, the opposite is true: a simple calculation based on average power is insufficient because of the characteristics of the production equipment. That is why at Technosens, we begin not by selecting an E-MATE model, but by analysing the actual requirements of the facility.

Technosens supplies industrial EEnovance energy storage systems and selects the appropriate configuration based on the facility’s load profile, solar PV system, generator, and existing power supply infrastructure.