The EEnovance E-MATE product range includes three models in this category:
-
E-MATE 105-221-A — 105 kW / 221 kWh
-
E-MATE 125-261-L — 125 kW / 261 kWh
-
E-MATE 200-418-L — 200 kW / 418 kWh
At first glance, the choice seems straightforward: the higher the load, the more powerful the BESS should be. However, for an industrial facility, power rating alone is not enough. The models differ in battery capacity, cooling method, connection voltage, and requirements for the facility’s electrical infrastructure. Sometimes, these parameters, rather than rated power, determine the configuration of the future system.
EEnovance E-MATE 105, 125 and 200 kW: Key Differences
| Specification | E-MATE 105-221-A | E-MATE 125-261-L | E-MATE 200-418-L |
|---|---|---|---|
| Rated power | 105 kW | 125 kW | 200 kW |
| Rated energy capacity | 221.056 kWh | 261.25 kWh | 418 kWh |
| Battery chemistry | LFP | LFP | LFP |
| Cell capacity | 314 Ah | 314 Ah | 314 Ah |
| Cooling | Air cooling | Liquid cooling | Liquid cooling |
| Rated AC voltage | 400 V | 400 V | 690 V |
| Enclosure protection rating | IP55 | IP55 | IP55 |
| Declared cycle life* | 8,000 cycles | 8,000 cycles | 8,000 cycles |
According to the manufacturer’s test conditions: 25 ± 2 °C, charging/discharging at 0.5P/0.5P, until 70% State of Health (SOH) is reached. Actual cycle life depends on operating conditions and usage patterns. The table shows that the E-MATE 105-221-A and E-MATE 125-261-L are relatively close in rated power but differ in battery capacity and cooling method. The E-MATE 200-418-L offers significantly higher power and energy capacity, as well as a different rated AC voltage of 690 V.
E-MATE 105-221-A: When Approximately 100 kW Is Required
The E-MATE 105-221-A has a rated power of 105 kW and a battery capacity of 221.056 kWh. Its battery system uses 314 Ah LFP cells and consists of 11 battery packs, each with a capacity of 20.096 kWh. The system operates at 400 V AC and uses air cooling for the batteries. This model can be considered for businesses requiring approximately 100 kW of BESS power. For example, the system can help offset part of the peak load, store surplus electricity generated by a solar photovoltaic (PV) system, or shift part of the facility’s electricity consumption to different hours. For many industrial facilities, the 400 V connection is a practical consideration. Air cooling also makes this model’s design simpler compared with systems that use a liquid cooling circuit.
E-MATE 125-261-L: Higher Capacity and Liquid Cooling
The E-MATE 125-261-L has a rated power of 125 kW and an energy capacity of 261.25 kWh. The battery system consists of five packs rated at 52.25 kWh each, using 314 Ah LFP cells. One of the main differences compared with the E-MATE 105-221-A is its liquid cooling system. During charging and discharging, battery cells generate heat. In systems with high battery packing density, a liquid cooling circuit allows more precise control of heat removal from the battery modules. However, liquid cooling alone does not automatically make one system better than another. The operating profile, ambient temperature, charging and discharging frequency, and maintenance requirements must also be considered. The difference in rated power between the 105 kW and 125 kW models is relatively small, just 20 kW. At the same time, the E-MATE 125-261-L provides approximately 40 kWh of additional battery capacity and uses a different thermal management system. Therefore, these two models should be compared not only by rated power but also by the intended battery operating profile.
E-MATE 200-418-L: 200 kW and an Important Voltage Consideration
The E-MATE 200-418-L has a rated power of 200 kW and a battery capacity of 418 kWh. The system contains eight battery packs rated at 52.25 kWh each, uses 314 Ah LFP cells, and features liquid cooling. Its enclosure protection rating is IP55.
However, there is another important parameter to consider when selecting this model: its rated AC voltage is 690 V. For a facility with an electrical distribution system based on 400 V, this must be considered during the design stage.
Depending on the power supply configuration, additional equipment may be required for voltage matching. Therefore, the approach of simply choosing the E-MATE 200-418-L because 200 kW is required is not sufficient.
The facility’s electrical network must first be analysed to determine where and how the BESS will be integrated. The E-MATE 200-418-L is worth considering for facilities that need to store and use several hundred kilowatt-hours of energy per cycle and whose electrical infrastructure can accommodate the required connection configuration.
105, 125 or 200 kW: What Determines the Right Choice?
The selection process should begin with the facility’s actual electrical load profile. Suppose a manufacturing plant consumes approximately 200 kW most of the time, but its load periodically increases to 300 kW. If the BESS is intended to offset this peak and keep grid consumption below 200 kW, approximately 100 kW of additional power is required. In this scenario, the E-MATE 105-221-A could be considered. However, if the facility plans to store significant amounts of surplus solar generation or shift larger quantities of energy between different periods of the day, battery capacity becomes a more important factor. In that case, it is necessary to compare not only the power ratings of 105, 125 and 200 kW but also the energy capacities of 221, 261 and 418 kWh.
In summary:
E-MATE 105-221-A — Suitable when approximately 100 kW of power is required, a 400 V connection is needed, and around 221 kWh of battery capacity is sufficient.
E-MATE 125-261-L — Worth considering when 125 kW of power and higher battery capacity are required, and liquid cooling is appropriate for the operating conditions.
E-MATE 200-418-L — Designed for applications requiring significantly higher power and approximately 418 kWh of stored energy. The connection configuration must account for its rated AC voltage of 690 V.
Can the System Be Expanded Later?
For industrial facilities, this question should be addressed before installing the first BESS, particularly if production expansion or increased solar PV capacity is planned. EEnovance supports parallel connection of systems on the AC side. The specific configuration depends on the model, equipment version, Energy Management System (EMS) architecture, electrical network parameters, and protection systems. Therefore, if future expansion is anticipated, scalability should be considered in the initial project design. For example, the official EEnovance website features a project in Linschoten, the Netherlands, using an E-MATE 125-261-L system with a rated power of 125 kW and an energy capacity of approximately 261 kWh. For facilities whose requirements exceed the 105–200 kW range, the EEnovance product portfolio also includes scalable FlexCore systems and G-Power solutions.
What Information Does Technosens Need to Select a BESS?
For a preliminary selection between the E-MATE 105, 125 and 200 kW models, the most important starting point is the facility’s actual electrical load profile. If short-term power peaks need to be analysed, data recorded at intervals of 15 minutes or less is preferable. In addition to the load profile, the following information is required:
- Electrical network parameters
- Installed solar PV capacity and generation profile, if applicable
- Production operating schedule
- Intended BESS application
- Plans for future system expansion
Based on these data, the required Power Conversion System (PCS) rating, battery capacity, and electrical connection configuration can be determined.
Technosens LLC supplies industrial EEnovance Battery Energy Storage Systems and helps select configurations based on the actual operating requirements of each facility.
In industrial projects, the largest BESS in the catalogue is not necessarily the best solution. The right system is one whose power rating, battery capacity, connection voltage, and integration configuration match the specific requirements of the facility.